Reeling & Trailing Cable Electrical Characteristics

 

A. Power Core Conductor Characteristic :

  • Nominal
    Conductor Area
    Strand Size Nominal
    Conductor
    Diameter
    Max. DC
    Resistance
    @20℃
    Max. AC
    Resistance
    @90℃*
    Nominal
    3-Phase
    Voltage Drop*
    Nominal
    Reactance*
    mm² no/mm mm Ω/km Ω/km mV/A.m Ω/km
    1.5 30/0.25 1.6 14.0 17.4 30.1 0.17
    2.5 50/0.25 2.0 8.37 10.5 18.2 0.15
    6 84/0.30 3.5 3.39 4.33 7.5 0.14
    10 77/0.40 4.6 2.02 2.58 4.5 0.13
    16 126/0.40 5.7 1.24 1.57 2.7 0.12
    25 209/0.40 7.6 0.746 0.936 1.6 0.11
    35 285/0.40 8.8 0.547 0.675 1.2 0.10
    50 380/0.40 10.1 0.410 0.523 0.92 0.10
    70 203/0.67 12.1 0.271 0.346 0.62 0.097
    70 570/0.40 12.4 0.271 0.346 0.62 0.096
    95 259/0.67 13.3 0.212 0.270 0.50 0.095
    95 475/0.50 14.5 0.208 0.266 0.49 0.093
    120 336/0.67 15.4 0.164 0.209 0.40 0.092
    120 608/0.50 16.2 0.162 0.208 0.39 0.091
    150 427/0.67 17.2 0.129 0.166 0.33 0.091
    150 777/0.50 18.1 0.127 0.163 0.32 0.089
    185 518/0.67 19.3 0.106 0.137 0.28 0.089
    240 672/0.67 23.0 0.0818 0.107 0.24 0.087
    300 854/0.67 24.5 0.0644 0.0847 0.21 0.086
  • *The AC characteristics are valid for up to 1.1/1.1kV operating voltage and can be used as a guide for higher operating voltages.

B. Continuous Current Carrying Capacity :

  • Power Conductor
    Nominal Area
    Cable Voltage Rating
    Protected From Sun Exposed To Sun
      1.1/1.1kV 3.3/3.3kV–33/33kV 1.1/1.1kV 3.3/3.3–33/33kV
    mm² A A A A
    1.5 23 18
    2.5 30 23
    6 49 38
    10 66 51
    16 88 89 67 66
    25 120 120 90 89
    35 145 145 110 105
    50 170 170 125 125
    70 220 220 160 155
    95 250 250 185 180
    120 295 295 210 210
    150 340 340 245 240
    185 385 385 270 265
    240 455 450 315 310
    300 515 510 355 350

C. Current Rating Factor :

  • Where the cable is wound on cylindrical or radial drum, the heat dispersion factor must be taken into consideration; therefore the current carrying capacity must be reduced by the derating factor:
  • Cylindrical Drum        
    Number of layer on drum 1 2 3 4
    Factor 0.85 0.65 0.45 0.35
  • Radial Drum Ventilated Unventilated
    Factor 0.85 0.75
  • Variations in ambient temperature for cable installed in air or in underground
  • Ambient Temp 15℃ 20℃ 25℃ 30℃ 35℃ 40℃ 45℃ 50℃ 55℃ 60℃ 65℃ 70℃ 75℃ 80℃ 85℃
    Conductor Temperature
    is 90℃
    1.26 1.20 1.15 1.10 1.05 1.0 0.94 0.88 0.81 0.73 0.65 0.57 0.47 0.34 0.19
  • Continues Current Rating above is calculated based on the IEC60287 Standard and Australian typical environment:
    40℃ air ambient temperature, 0.8 solar radian absorption coefficients and 1000W/m² and the value is for guidance only.